美国vanguard CT-7000 S3断路器时间机械特性 

美国vanguard CT-7000 S3断路器时间机械特性

  • 品 牌:美国vanguard
  • 价 格:面议 /
  • 供 应 地:上海上海市
  • 包装说明:0
  • 产品规格:0
  • 运输说明:0
  • 交货说明:0
  • 发布日期:2016/2/29 17:13:55
  • 联系人QQ:2732723830 点击这里给我发消息

详细说明

详细说明Explain

美国vanguard CT-7000 S3断路器时间机械特性
美国vanguard CT-7000 S3断路器时间机械特性测试仪Digital Circuit Breaker Analyzer
The CT-7000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-7000 S3 is available with 3 (part number 9021-UC) or 6 contact timing channels (part number 9100-UC). The CT-7000 S3 can fully analyze a circuit breaker's performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Both contact and motion analysis can be performed on all circuit breaker operations (OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN, and OPEN CLOSE-OPEN). The CT-7000 S3's timing WINOOW is selectable between 1 second, 10 seconds, and 20 seconds.
Fully analyze circuit breaker's performance by measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
USB computer interface
USB Flash drive interface (Flash drive not included)
Store up to 200 test records and 100 test plans internally
Initiate Breaker Operation
Built-in 4.5" wide Thermal Printer
Rugged "QWERTY" style membrane keypad
Optional "On-line" Timing Mode
Optional dual ground testing mode
Optional Bluetooth wireless computer interface
CT-7000 S3
Technical Specifications

TYPE Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONS 14”W x 21 K” L x 8” D (35 cm x 53 cm x 20 cm); 15 lbs (6.8 Kg)
INPUT POWER 100-240Vac, 3A, 50/60Hz
DRY-CONTACT INPUTS 3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time.
TIMING WINOOWS 1 second, 10 seconds, or 20 seconds
TIMING RESOLUTIONS ±50 micro-seconds @ 1 sec. duration,
±500 micro-seconds @ 10 sec. duration,
±1.0 milli-seconds @ 20 sec. duration
TIMING ACCURACY 0.05% of reading ±0.05 ms @ 1 second duration
DRY-CONTACT CHANNEL PROTECTION All contact inputs are grounded until test. Input channels are also protected against static discharge.
DRY-CONTACT DETECTION RANGE Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
INSERTION RESISTOR DETECTION RANGE 50 – 5,000 ohms
TRIGGER INPUT VOLTAGE Open/Close trigger voltage: 24 V – 300V DC or peak AC
VOLTAGE SENSING INPUT RANGE V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
BREAKER OPERATIONS Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY 30A, 250 Vac/dc max
INITIATE CURRENT READING RANGE one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
DIGITAL TRAVEL TRANSDUCER INPUTS 3 channels, 200 ohm – 10K ohms
CONTACT TRAVEL POINT DIFFERENCE measures “slow-close” contact-point distances; results can be printed
DISPLAY back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
PRINTER built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGE Store up to 200 test records and 100 test plans
EXTERNAL TEST RECORD STORAGE USB Flash drive interface for external storage of test records and test plans
COMPUTER INTERFACES One USB port, optional Bluetooth wireless interface
PC SOFTWARE WINOOWs? based Breaker Analysis software included with purchase price
CABLES furnished with full set of test leads
OPTIONS transportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
bluetooth interface
SAFETY designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
ENVIRONMENT Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifi cations
WARRANTY one year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).


美国vanguard CT-8000 S3断路器时间机械特性测试仪Digital Circuit Breaker Analyzer
The CT-8000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-8000 S3 is available with 3 (part number 9103-UC) or 6 contact timing channels (part number 9104-UC). The CT-8000 S3 can fully analyze a circuit breaker's performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Also, an outstanding feature of the CT-8000 S3 is the ability to perform dynamic resistance tests on circuit breaker contacts.
Fully analyze circuit breaker's performance by measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
Perform dynamic contact resistance test
USB computer interface
USB Flash drive interface (Flash drive not included)
Store up to 200 test records and 100 test plans internally
Initiate Breaker Operation
Built-in 4.5" wide Thermal Printer
Rugged "QWERTY" style membrane keypad
Optional "On-line" Timing Mode
Optional dual ground testing mode
Optional Bluetooth wireless computer interface
       
CT-8000 S3
Technical Specifications
 
       
TYPE Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONS 16”W x 11”H x 14”D (40.6 cm x 29.9 cm x 35.6 cm); Weight: 22 lbs (9.98 kg)
INPUT POWER 100-240Vac, 10A, 50/60Hz
DRY-CONTACT INPUTS 3 channels (9103-UC) or 6 channels (9104-UC). Channel can detect the main contact and resistor contact time.
TIMING WINOOWS 1 second, 10 seconds, or 20 seconds
TIMING RESOLUTIONS ±50 micro-seconds @ 1 sec. duration,
±500 micro-seconds @ 10 sec. duration,
±1.0 milli-seconds @ 20 sec. duration
TIMING ACCURACY 0.05% of reading ±0.05 ms @ 1 second duration
DRY-CONTACT CHANNEL PROTECTION All contact inputs are grounded until test. Input channels are also protected against static discharge.
DRY-CONTACT DETECTION RANGE Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
INSERTION RESISTOR DETECTION RANGE 50 - 5,000 ohms
TRIGGER INPUT VOLTAGE Open/Close trigger voltage: 24 V – 300V DC or peak AC
VOLTAGE SENSING INPUT RANGE V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
BREAKER OPERATIONS Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY 30A, 250 Vac/dc max
INITIATE CURRENT READING RANGE one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
DIGITAL TRAVEL TRANSDUCER INPUTS 3 digital travel transducer channels; linear range: 0.0 – 60.0 in (±0.01 in)
rotary range: 0 – 360 degrees (±0.36 degrees)
RESISTOR TYPE TRANSDUCER INPUTS 3 channels, 200 ohm – 10K ohms
CONTACT TRAVEL POINT DIFFERENCE measures “slow-close” contact-point distances; results can be printed
DYNAMIC/STATIC RESISTANCE RANGE 0.1 – 1,999 micro-ohms; accuracy: ±2% of reading, ±5 micro-ohms
RESISTANCE TEST CURRENT 200 amperes max
DISPLAY back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
PRINTER built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGE Store upt to 200 test records and 100 test plans
EXTERNAL TEST RECORD STORAGE USB Flash drive interface for external storage of test records and test plans
COMPUTER INTERFACES One USB port, optional Bluetooth wireless interface
PC SOFTWARE WINOOWs? based Breaker Analysis software included with purchase price
CABLES furnished with full set of test leads
OPTIONS transportation cases (available for the CT-8000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
bluetooth interface
SAFETY designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
ENVIRONMENT Operating: -10°C to +50°C (+15°F to +122°F);
Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY 90% RH @ 40°C (104°F) non-condensing
ALTITUDE 2,000 m (6,562 ft) to full safety specifi cations
WARRANTY one year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
 
OPTIONAL TESTING FEATURES
  ON-LINE TIMING MODE
ON-LINE CURRENT SENSOR three non-contact AC current sensors, range 0-100 amperes
ON-LINE DC CURRENT SENSOR one non-contact DC current sensor, range 0-20 amperes
  DUAL GROUND TIMING MODE
DUAL GROUND CLAMP-ON PROBES 3 non-contact clamp-on probes



 

卖家名片Cards

卖家名片

上海山合海融商贸有限公司

联系人:孙宝金(市场部经理)

手机:13818244503

邮箱:biz@shhairong.cn

地址:上海上海市陆翔路678弄60号

电话: 传真:

旺铺

在线询盘/留言Online Inquiry

  • *您的姓名:

  • *联系手机:

  • 固话电话:

  • E-mail:

  • 所在单位:

  • 需求数量:

  • *咨询内容:

免责声明:交易有风险,请谨慎交易,以免因此造成自身的损失,本站所展示的信息均由企业自行提供,内容的真实性、准确性和合法性由发布企业负责。本站对此不承担任何保证责任。
商国互联供应商 品质首选

上海山合海融商贸有限公司

  • 联系人:孙宝金(市场部经理)
  • 手机:13818244503
  • 电话:
  • 会员级别:试用会员
  • 认证类型:企业认证
  • 企业证件:已通过企业认证 [已认证]
  • 认证公司:
  • 主营产品:测试仪 兆欧表 电容器 过电压保护器 接地线 验电器 绝缘靴 绝缘手套 绝缘毯 继电器 熔断器 电阻器 避雷器 互感器 测高仪 核相仪
  • 公司所在地:上海上海市